UEC
Menu
UEC
en
en
 Modular energy equipment Modular energy equipment
Modular energy equipment
Circuit breakers
Circuit breakers
Circuit breakers GEWISS
Circuit breakers UEC
Differential protection equipment
Differential protection equipment
Differential protection devices GEWISS
Differential protection devices UEC
Additional modular equipment
Additional modular equipment
Additional modular devices GEWISS
Additional modular devices UEC
High power protection and connection equipment High power protection and connection equipment
High power protection and connection equipment
Switch disconnectors
Switch disconnectors
Switch disconnectors and additional devices GEWISS
Switch disconnectors and additional devices UEC
Fuses
Fuses
Fuses and adiitional devices GEWISS
Fuses and adiitional devices UEC
Compressed-air circuit breakers and additional devices
Compressed-air circuit breakers and additional devices
Compressed-air circuit breakers and additional devices UEC
Moulded case circuit breakers and additional devices
Moulded case circuit breakers and additional devices
Moulded case circuit breakers and additional devices GEWISS
Moulded case circuit breakers and additional devices UEC
Registration, control, measure, and power supply equipment Registration, control, measure, and power supply equipment
Registration, control, measure, and power supply equipment
Power supply equipment
Power supply equipment
Power supply equipment UEC
Enclosures, boxes and accessories Enclosures, boxes and accessories
Enclosures, boxes and accessories
Metal enclosures
Metal enclosures
Metal enclosures GEWISS
Metal enclosures UEC
Plastic boxes
Plastic boxes
Plastic boxes GEWISS
Plastic boxes UEC
Accessories and accessories for cabinets
Accessories and accessories for cabinets
Enclosures' accessories GEWISS
Enclosures' accessories UEC
Cable carrying systems Cable carrying systems
Cable carrying systems
Cable trunking and accessories
Cable trunking and accessories
Cable trunking and accessories UEC
Junction boxes
Junction boxes
Junction boxes GEWISS
Junction boxes UEC
Metal cable trays and accessories
Metal cable trays and accessories
Metal cable trays and accessories UEC
Metal conduits, pipes, and accessories
Metal conduits, pipes, and accessories
Metal conduits, pipes, and accessories UEC
Plastic conduits and pipes
Plastic conduits and pipes
Plastic pipes GEWISS
Plastic pipes UEC
Switches, sockets, plugs, and extension cords Switches, sockets, plugs, and extension cords
Switches, sockets, plugs, and extension cords
Connectors, sockets and adapters
Connectors, sockets and adapters
Connectors, sockets and adapters UEC
Domestic extension cords and supply-line filters
Domestic extension cords and supply-line filters
Domestic extension cords and supply-line filters UEC
Domestic switches, sockets, and plugs
Domestic switches, sockets, and plugs
Domestic switches, sockets, and plugs GEWISS
Domestic switches, sockets, and plugs UEC
High power extension cords
High power extension cords
High power extension cords UEC
High power sockets and plugs
High power sockets and plugs
High power sockets and plugs GEWISS
High power sockets and plugs UEC
Industrial sockets and plugs
Industrial sockets and plugs
Industrial interlocked sockets GEWISS
Industrial sockets and plugs GEWISS
Cross-connection and management equipment Cross-connection and management equipment
Cross-connection and management equipment
Actuators, switches
Actuators, switches
Actuators, switches UEC
Command and signal devices
Command and signal devices
Command and signal devices GEWISS
Command and signal devices UEC
Contactors
Contactors
Contactors UEC
Contactors' additional devices
Contactors' additional devices
Contactors' additional devices UEC
Supervisory and managing relay
Supervisory and managing relay
Supervisory and managing relay UEC
Wiring equipment and instrument Wiring equipment and instrument
Wiring equipment and instrument
Isolating, binding, and marking items
Isolating, binding, and marking items
Isolating, binding, and marking items UEC
Lugs, sleeves, connectors, and couplers
Lugs, sleeves, connectors, and couplers
Lugs, sleeves, connectors, and couplers UEC
Instruments
Instruments
Lighting Lighting
Lighting
Industrial lighting
Industrial lighting
Industrial lighting GEWISS
Office lighting
Office lighting
Office lighting UEC
Office lighting GEWISS
Road and street lighting
Road and street lighting
Road and street lighting UEC
Road and street lighting GEWISS
Smart lighting
Smart lighting
Smart lighting GEWISS
  • Where to buy
  • Education
    Education Educational resources
  • Support
    Technical support and documentation Promotion
  • Implemented projects
  • Sales
  • Novelty Novelty
  • Designers
  • About the company
    About Us News Contacts Questions and answers Cooperation with us
  • Blog

Article Contents

Key takeaways
Why a generator and an inverter need an ATS
How an ATS works with a generator: the overall logic
The ATS wiring diagram for a generator (grid-generator)
Where to place the ATS in the panel: order of devices
Does an inverter need an external ATS, or is the built-in bypass enough?
Why you must not feed a generator into a socket
How to choose the ATS pole configuration: 2P or 4P?
How to earth the generator and what to do with the neutral
Questions and answers (FAQ)

ATS for a Generator and Inverter: Wiring Diagram and Installation

Oleg Lukianchuk

Oleg Lukianchuk

Technical Training Engineer
Updated: 20 july 2026
Article Contents
Key takeaways
Why a generator and an inverter need an ATS
How an ATS works with a generator: the overall logic
The ATS wiring diagram for a generator (grid-generator)
Where to place the ATS in the panel: order of devices
Does an inverter need an external ATS, or is the built-in bypass enough?
Why you must not feed a generator into a socket
How to choose the ATS pole configuration: 2P or 4P?
How to earth the generator and what to do with the neutral
Questions and answers (FAQ)

Key takeaways

An ATS for a generator and inverter transfers the house load from the grid to the backup source in 50 ms (UEC SB-ATS series) and guarantees that the link between the sources is broken. The transfer switch is installed after the electricity meter and the main circuit breaker, ahead of the group breakers.

Key point: feeding a generator into an ordinary socket is prohibited — it creates backfeed into the external line. In a "grid ↔ battery" scheme a hybrid inverter usually needs no external ATS, but as soon as a generator enters the system, a dedicated transfer switch is required.

Hello! This material was prepared by the UEC engineering department. We manufacture the SB-ATS series of automatic transfer switches and specify backup power panels every day, so we show the diagrams the way a qualified electrician actually builds them, not as a simplified picture.

This article is about the wiring diagram: where to run the line, neutral and earth, where the ATS sits in the panel, and how the hybrid-inverter scenario differs from the generator one. Rating calculation by power and the interlocking principle are only mentioned briefly here — they are covered in detail in the complete ATS guide.

⚠ WARNING! Working with electrical equipment is life-threatening!

Connecting an ATS and a backup power supply (especially a generator input) involves the risk of backfeed and requires a qualification of at least electrical safety group III. Have the installation carried out by a licensed electrician.

Why a generator and an inverter need an ATS

An ATS is needed so that the backup source picks up the load automatically and so that the grid and the generator are never connected to each other. Without a transfer switch, any backup power supply becomes either a manual operation or a source of accidents.

Generator

Requires a transfer device

A generator supplies the house only when the grid is gone, so a device is needed to disconnect the grid and connect the generator. If a person does this, a manual 1-0-2 changeover isolator is used. If the transfer must happen without the owner present, an automatic transfer switch is installed: it monitors the presence of voltage itself and moves the load within tens of milliseconds.

Inverter

Often has its own logic

An inverter (especially a hybrid one) often has its own transfer logic, so it does not always need an external ATS — there is a separate section on this below. What an ATS does NOT do: it does not increase the generator's power, it does not switch on the whole house at once, and it does not start the generator engine by itself without the corresponding auto-start logic.



Home power sources — grid, generator and inverter routed through an automatic transfer switch.

How an ATS works with a generator: the overall logic

The ATS constantly monitors the voltage of the main source and, as soon as the grid disappears, transfers the load to the backup after a short delay; when the grid returns, it moves the load back. The transfer follows the break-before-make principle: the contacts of one source open BEFORE the contacts of the other close, so the two sources are never connected at the same time [4].

The operating logic in automatic mode consists of several steps:

  • The grid disappears — the ATS registers the absence of voltage.
  • The ATS disconnects the grid input (opens the contacts).
  • A command is issued to the backup source; for a generator with electric start this is the engine start command, after warm-up (typically 5-10 minutes for the manual scenario) [4].
  • The ATS closes the generator contacts — the load is supplied from the backup source.
  • The grid returns — after a return delay the ATS opens the generator and switches the grid back on.

An important limitation:

for fully automatic engine starting, the generator must have an electric start. The UEC SB-ATS series performs load switching itself (automatically or manually) — the engine auto-start function is provided by separate generator auto-start logic, so these two units are selected together [7].



The automatic transfer sequence to the generator — five steps from grid failure to restoration.

The ATS wiring diagram for a generator (grid-generator)

The basic diagram has three groups of terminals: the grid input, the generator input and the output to the load (the consumer panel). The ATS switches the line and neutral of both sources onto a common output, while the protective conductor PE runs straight through and is not switched.

The conductor sequence in principle:

  • The line L of the grid goes to the grid input terminal of the ATS; the line L of the generator goes to the generator input terminal; the outgoing line goes to the load panel.
  • The neutral N of a multi-pole transfer switch is switched together with the lines — to isolate the house from the second source completely and avoid creating a parallel link between the neutrals [3].
  • The PE (earth) is not broken by the transfer switch: the generator frame must be bonded to the building's earthing system, and the load's PE remains continuous [3].

Below is a clean vector diagram of a single-phase grid-generator input through an ATS. The exact switching of neutral and earth depends on the site's earthing arrangement (TN-C-S, TN-S) and is agreed with the electrician.

Single-phase grid-generator input diagram through a 2P ATS L — line N — neutral PE — earth — junction — terminal Grid 230 V after the meter and the main breaker Generator frame bonded to PE PE to the frame grid input generator input L N L N ATS SB-ATS 2P break-before-make 50 ms position 1 — grid L N output to the load Load panel backup group of consumers PE — continuous bar, bypasses the ATS PE is not switched. Break-before-make — simultaneous connection of the sources is ruled out.
Diagram 1. Single-phase grid-generator input through a 2P ATS: line L and neutral N of both sources are switched together, while PE runs straight past the transfer switch to the panel and by a separate branch to the generator frame.

For a three-phase supply the logic is the same, but three lines L1/L2/L3 are switched together with the neutral (4P), and the PE likewise stays continuous.

Where to place the ATS in the panel: order of devices

The ATS is installed after the electricity meter and the main circuit breaker of the grid, but before the consumer group breakers — so that it only governs the choice of source, while protection and metering stay in their places [2]. This is a requirement of the State Energy Supervision authority and a key safety condition: the source transfer switch must not be installed ahead of the meter.

The typical sequence in the panel from the supply to the consumer:

Position Device Purpose
1 Grid input Cable from the utility meter
2 Main circuit breaker Protection and manual disconnection of the grid
3 ATS (SB-ATS) Source selection: grid or generator
4 Generator input Separate cable from the generator (via its own breaker)
5 Voltage relay (if required) Protection against over/undervoltage of the backup source
6 Group breakers / RCD Distribution to the backup group of consumers

The meter comes before the ATS — backup power is also metered or, depending on the utility's scheme, the generator branch is taken out separately; this is agreed with the distribution system operator. A voltage relay is often installed next to the ATS, because the voltage from a domestic generator can be unstable, and both devices work together in the panel.

Order of devices in the panel: where the ATS sits L — line N — neutral PE — earth — junction Meter utility metering 1 Main breaker protection and manual disconnection of the grid 2 ATS SB-ATS source selection: grid or generator 3 Voltage relay if required (surge protection) 5 Group breakers backup group of consumers 6 L N grid supply Generator backup source Generator breaker 4 generator input PE — separate continuous bar (does not enter the meter or the ATS) PE to consumers PE to the frame The ATS goes after the meter and the main breaker, before the group breakers.
Diagram 2. Order of devices in the panel: meter → main breaker → ATS → voltage relay (if required) → group breakers. The generator enters by a separate branch through its own breaker; PE is run as a separate continuous bar.

Does an inverter need an external ATS, or is the built-in bypass enough?

If the task is only to switch between the grid and the battery, a hybrid inverter is usually served by its built-in bypass (transfer relay): it takes the load onto the battery itself within a few milliseconds when the grid fails [5]. An external ATS becomes necessary when a generator is added to the scheme as a separate source.

Let us look at the two scenarios separately, because this is exactly where most online advice gets confused.

When is the inverter's built-in bypass enough?

The built-in bypass is enough in a grid ↔ battery scheme, where the backup source is only the battery. In grid mode a hybrid inverter supplies the load directly from the grid and, when the grid fails, switches to battery power through the inverter almost without a pause — no external transfer switch is needed for this [5]. This is the classic home UPS/hybrid setup without a generator.

When does an inverter need an external ATS?

An external ATS is required in a grid ↔ generator ↔ inverter scheme, when you need to choose automatically between the grid and the generator, control the generator auto-start and guarantee separation of the sources [5]. A dedicated transfer switch is also installed when the inverter has no generator input, or when the generator is to supply the house as an independent backup source rather than merely charge the battery.

Where should the generator's AC input be connected on a hybrid inverter?

The generator is connected to the input the manufacturer intended: to a dedicated GEN port if there is one, or to the common AC-in (grid-in) — but only if the manual permits it and the generator's parameters are compatible [5]. On models with a separate GEN port, that is where the priority and charge current settings are available; that is why the generator-to-inverter wiring is checked against the specific model's datasheet rather than built from a generic picture.

A brief comparison of the two solutions:

Criterion Inverter's built-in bypass External ATS
Sources Grid ↔ battery Grid ↔ generator (↔ inverter)
Transfer Internal, milliseconds External, tens of milliseconds
Generator control None Yes, with auto-start
Separation of sources Within the inverter Guaranteed, a dedicated device
When to choose it Battery-only backup A generator is part of the scheme



Comparison of the inverter's internal grid-battery bypass and an external ATS for a generator.

Why you must not feed a generator into a socket

Connecting a generator into an ordinary socket in the building without a transfer switch is prohibited, because it creates backfeed — the generator sends voltage back into the external line, which an emergency crew may believe to be de-energised [2][5]. This is a lethal hazard for line workers and a risk of short circuit and fire.

Approximate socket ratings according to the State Energy Supervision authority: a 10 A socket withstands about 2.2 kW, a 15 A one about 3.5 kW [2]. A powerful generator must not be fed through such a socket even temporarily — the current will exceed the value the socket is rated for. There is only one correct route: the generator input goes through a transfer switch (an ATS or a manual 1-0-2 changeover isolator) with interlocking against simultaneous connection of the sources, installed after the meter and the main breaker [2].

Why a generator must not be fed into a socket: backfeed and the correct input ✖ PROHIBITED generator cabled into an ordinary socket external line (believed to be de-energised) ! emergency crew Meter and panel no transfer switch domestic socket 10 A ≈ 2.2 kW · 15 A ≈ 3.5 kW Generator cable into a socket backfeed current Voltage travels back into the external grid — a lethal hazard for line workers. ✓ CORRECT input through an interlocked transfer switch grid Meter + main breaker ATS or changeover 1-0-2 break-before-make generator inlet Generator through the inlet Load panel backup group The sources are never connected: an inlet does not replace a transfer switch.
Diagram 3. On the left — the forbidden scheme: a generator in a domestic socket creates backfeed into the external line. On the right — the correct input: a generator inlet and a transfer switch (an ATS or a 1-0-2 changeover isolator) with guaranteed separation of the sources.

Do not confuse an ordinary domestic socket with a generator inlet (an input connector). An inlet is a dedicated fixed input connector on the wall of the house, through which the cable from the generator enters the panel and is necessarily switched by a transfer switch (a 1-0-2 changeover isolator or an ATS) with interlocking. The inlet does not replace the transfer switch, it merely provides a safe place to connect the cable; the prohibition concerns precisely feeding a generator into an ordinary domestic socket without a transfer switch.

What must NOT be present in the scheme (YMYL safety checklist):

  • There is no direct connection between the generator and a socket in the house.
  • There is no possibility of closing the grid and the generator at the same time (break-before-make interlocking is mandatory).
  • There is no switching of the PEN conductor as a working conductor — it is not broken.
  • There is no generator input ahead of the meter and the main breaker.

How to choose the ATS pole configuration: 2P or 4P?

The pole configuration is chosen according to the supply scheme: for a single-phase 230 V grid you take 2P (line L and neutral N are switched), for a three-phase 400 V grid — 4P (three lines L1/L2/L3 plus neutral N) [3]. The neutral is broken synchronously with the lines, in order to isolate the house from the second source completely.

ATS pole configuration: 2P for a single-phase grid and 4P for a three-phase one lines L neutral N PE — not switched 2P — single-phase grid 230 V line L and neutral N are switched L N ATS 2P 2 poles SB-ATS-2-063 to the load PE continuous bypasses the device Single-phase input: line and neutral are broken. 4P — three-phase grid 400 V L1, L2, L3 and neutral N are switched L1 L2 L3 N ATS 4P 4 poles SB-ATS-4-063 · SB-ATS-4-100 to the load PE continuous bypasses the device Three-phase input: the neutral is broken synchronously with the lines. The pole configuration follows the actual scheme of both sources, not the "theoretical" supply.
Diagram 4. Transfer switch pole configuration: 2P for a single-phase 230 V grid (line + neutral) and 4P for a three-phase 400 V grid (three lines + neutral). In both cases the protective conductor PE bypasses the device and is not switched.

Mapping to the UEC SB-ATS line:

Model Poles Current For which grid
SB-ATS-2-063 2P 63 A Single-phase 230 V
SB-ATS-4-063 4P 63 A Three-phase 400 V
SB-ATS-4-100 4P 100 A Three-phase 400 V, higher load

The rating of the transfer switch must equal or exceed that of the main circuit breaker and the calculated load of the backup group, with a current margin [6]. We do not repeat the detailed rating calculation by the power formula or the 10-30% margin principle here — they are covered step by step in the complete ATS guide. What matters here is something else: only the critical group of consumers should be backed up (heating boiler, circulation pump, refrigerator, lighting), because a generator is usually weaker than the grid and will not carry the whole house [6].

What to do if the generator and the grid have different phase configurations

A common case: the grid supply is three-phase (400 V) while the generator is single-phase (230 V). A universal "just use 4P" is not enough here. If a three-phase house is backed up by a single-phase generator, only the critical single-phase group is supplied from the backup source: it is separated out and routed through a transfer switch of the corresponding pole configuration, while the remaining phases are left without backup. A three-phase generator feeding a single-phase load is connected with one phase, distributing the power evenly across the windings so as not to overload one of them. The number of poles of the transfer switch is chosen according to the actual scheme of both sources, not the "theoretical" supply; matching the phases and neutral with different phase configurations is a designer's task, because a mistake creates imbalance and dangerous operating modes.

How to earth the generator and what to do with the neutral

The generator frame must be bonded to the building's PE system, and when the generator is connected, the neutral is broken synchronously with the lines by a multi-pole transfer switch [3]. The exact neutral and earth arrangement depends on the site's earthing system (TN-C-S, TN-S) and on the generator type, so it is settled by the electrician according to the equipment datasheet.

⚠ An honest limitation: there is no universal answer of "always 4P and always break the neutral" — in a TN-C-S arrangement the generator may be a separately earthed source, and then the switching of the neutral depends on how the neutral and the protective conductor are connected on site [3]. A PEN conductor is not switched as a working conductor. This is exactly why the generator input is the case where the scheme must be agreed with a qualified electrician rather than assembled from a generic picture found online.

If you are still choosing between automatic and manual transfer for a generator, the comparison of scenarios and costs is covered in the article ATS or manual transfer switch; and how to build a manual generator input specifically is covered in the article on the 1-0-2 changeover isolator. Typical operating and maintenance mistakes with an ATS are collected separately in the material on common ATS mistakes.

Questions and answers (FAQ)

❓ Can a generator be plugged into a socket in the house?

No. This creates backfeed into the external line and poses a lethal hazard to emergency crews. A generator is brought in only through a transfer switch (an ATS or a 1-0-2 changeover isolator) with interlocking, installed after the meter and the main breaker [2].

❓ Does the generator need to be earthed?

Yes, the generator frame must be bonded to the building's PE earthing system. The exact neutral and earth arrangement depends on the site's earthing system and is agreed with the electrician [3].

❓ Should you choose 2P or 4P for an ATS?

2P — for a single-phase 230 V grid (line + neutral), 4P — for a three-phase 400 V grid (three lines + neutral). The neutral is broken together with the lines [3].

❓ Does an inverter's built-in bypass replace an external ATS?

In a grid ↔ battery scheme the built-in bypass is enough. An external ATS is needed when the system includes a generator as a separate source with auto-start and guaranteed separation of grid and generator is required [5].

❓ Why does the generator breaker trip after transferring to the backup source?

Most often this is an overload: more consumers are connected to the backup group than the generator can carry, or powerful loads with a high inrush current start simultaneously. Only the critical group should be backed up, matched to the generator's real output [6].

Automatic transfer switch ATS SB-ATS-2-063-UEC
Automatic transfer switch ATS SB-ATS-2-063-UEC
2 376.90грн
Add to list
Automatic transfer switch ATS SB-ATS-4-063-UEC
Automatic transfer switch ATS SB-ATS-4-063-UEC
2 895.10грн
Add to list
Transfer Switch SB-H09-63 2P 63А UEC
Transfer Switch SB-H09-63 2P 63А UEC
423.40грн
Add to list
Transfer Switch SB-H09-63 3P 63А UEC
Transfer Switch SB-H09-63 3P 63А UEC
544.30грн
Add to list
Transfer Switch SB-H09-63 4P 63А UEC
Transfer Switch SB-H09-63 4P 63А UEC
855.90грн
Add to list
Automatic transfer switch ATS SB-ATS-4-100 UEC
Automatic transfer switch ATS SB-ATS-4-100 UEC
3 623.40грн
Add to list
Not confident in the choice?
Our engineers will help you choose the equipment and calculate the network according to PUE standards
Get a consultation
Oleg Lukianchuk

Oleg Lukianchuk

Technical Training Engineer
12+ years of experience in electrical engineering. He rose through the ranks from Electrician to Head of the Laboratory. Since 2021, he has served as a Technical Training Engineer, conducting seminars, consulting partners, and creating expert product vide
Facebook Email Instagram All articles by author
Read also
Manual Changeover Switch 1-0-2: What It Is and How to Choose
Articles

Manual Changeover Switch 1-0-2: What It Is and How to Choose

Oleg Lukianchuk

Oleg Lukianchuk

27 july

ATS for a Generator and Inverter: Wiring Diagram and Installation
Articles

ATS for a Generator and Inverter: Wiring Diagram and Installation

Oleg Lukianchuk

Oleg Lukianchuk

20 july

ATS (Automatic Transfer Switch): The Complete Guide
Articles

ATS (Automatic Transfer Switch): The Complete Guide

Oleg Lukianchuk

Oleg Lukianchuk

13 july

UEC

© UEC 2026.

Contacts
Our location
Address:
03062, Ukraine, Kyiv, 67 Beresteyskyi (Peremohy) ave., BC "BRIGHT"
Our
Phone number:
+38 (044) 354 00 02
Our mail
Email:
support@uec-ua.com
  • Privacy Policy
  • Сatalog
  • Where to buy
Become a partner
Send
By clicking the "Submit" button, you agree to the privacy policy
Register a project
Load the title page of the project*
Load project specification*
Send
By clicking the "Submit" button, you agree to the privacy policy
Register for training
Send
By clicking the "Submit" button, you agree to the privacy policy